DRX-FP
FREQUENCY/PULSE SIGNAL CONDITIONER

Made in the USA
INFINITY
Electromagentic Compatibility
Year 2000 Compliant
What You need:
ò Your choice of the signal conditioner
ò IBM PC or compatible
ò Windows 3.1 or higher, or Windows 95
ò RJ12 connector with telephone cable
ò Adapter (DB9/25 to RJ12)
SETTING UP YOUR SYSTEM
DRN Computer Connection
INPUT TYPE
Min. Low level signal input (magnetic pickups): From 0 mV to 120 mV
Input Type

0.1 uF capacitor

Open Collector NPN (Use software to set: 3 Kohm pull up to 5V): Max. current source = 1.66 mA

Open Collector PNP (Use software to set: 1Kohm pull down to RTN): Max. current sink = 12.5 mA

TTL/CMOS Input: (Use software to set: no pull up/down).
Low <= 0.8 V , High >= 3.5 V (For Input: 0.2 Hz to 16 KHz)
Low <= 0.8 V , High >= 12 V ( For Input: 0.2 Hz to 50 KHz )

NAMUR Sensors
(Use software to set: 1Kohm pull down to RTN and 8.2V Excitation.)

For measuring a low level signal riding on top of a large DC signal, connect a 0.1 uF capacitor. See Detail. Use software to set 1Kohm pull down to RTN.

OPERATING MODES
DRX-FPFREQUENCY RANGE:
Range = 0.2 Hz to 50 KHz

Totalize with Reset: Range = 0 to 999999, if reading is larger than 999999, then reading is converted to floating point number, i.e. 9.99E9 (maximum).

A-B Totalize (Reset input used as +A input): Range = -99999 to 999999, if reading is larger than 999999, then reading is converted to floating point number, i.e. -9.99E9 (minimum), 9.99E9 (maximum).

Quadrature (Reset input used as second input): Range = -99999 to 999999, if reading is larger than 999999, then reading is converted to floating point number, i.e. -9.99E9 (minimum), 9.99E9 (maximum).

ISOLATION

Three way isolation up to 1800 V Peak for 1 minute, 354 V Peak continuous per IEC spacing.
  • Normal mode rejection 60dB
  • Common mode rejection 100dB

  • INPUT OVER-CURRENT PROTECTION

  • 10% Above full scale continuously
  • 100% Above full scale for 10 seconds

  • INPUT IMPEDANCE
    Input:
    1Mohm to +EXC
    Reset:
    100K to +5V

    INPUT OVER-VOLTAGE PROTECTION
    With 1K pull down:
    14V
    With 3K pull up: 20V
    Without pull up/down:
    60V

    EXCITATION
    5, 8.2 or 12.5V at 25mA, programmable

    ACCURACY AT 25 ░C
    ▒ 0.1% of FS Crystal time base accuracy:
    ▒ 50 ppm

    TEMPERATURE STABILITY
  • ▒ 50 ppm/░C typical
  • Time base stability: ▒ 1ppm/░C

  • STEP RESPONSE FOR RS485 OUTPUT

    0.1 second to 99% of the final value
    (Filter time constant = 0, Gate time = 0.05 Sec)

    RESPONSE TIME

    To verify the response time, check the carriage return <CR>, it will be sent at the end of the response. You can send another command after you receive the <CR>.

    i.e. send: *01X01 / response: 01X01
    Note: Only for reading (X01 command). 01 is address.

    Frequency mode: response time is controlled by the gate time. If gate time is increased then response time is longer.

    Other modes: response time is not controlled by the gate time.

    Signal Conditioner
    WARM UP TO RATED ACCURACY
    30 minutes

    INPUT POWER

    10 to 32 Volt

    DC POWER CONSUMPTION

    3 Watts (125 mA at 24 V DC)

    OPERATING AMBIENT

    -5 to +55 ░C

    STORAGE TEMPERATURE

    -40 to +85 ░C

    RELATIVE HUMIDITY

    90% at 40 ░C non-condensing
    Help Price List Specifications Print Manual Manuals Home
     Home Home  Table of Contents TOC  Back Back  Next Next